Contact us For registered customers Lietuvių По-русски


Choose specification
Number of cores:
Choose cross-sectional area, mm²:


The wire is designed for fixed installation, to lay beneath the plaster or in waterproof cable ducts.

Solid conductor is made out of annealed aluminum wires. Aluminum conductor are PVC-insulated.

Additional information

The wire fully complies with the EU Directive 2011/65/ES on the Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment.

The wire fully conforms to the requirements of the EU Directive 2006/95/EB for Low Voltage.

The cable conformed with Regulation (EU) No 305/2011 of the European Parliament and of the Council.

Reaction to Fire Class Eca. DoP (Declaration of Performance LK-DoP 10/001/EN)

Technical date
Conductor resistance at +20°C In accordance with GOST 22483-77
Conductor working temeprature, max. +70°C (under normal conditions) 160°C (in the event of short circuit)
Thermal shock 1 h at +150°C
Rated voltage U/U0 450/750 V
High voltage test, kV 2,5 kV
Operating temperatures Mounting -5°C - +40°C Operating -30°C - +70°C
Flame propagation Flame test in accordance with LST EN 60332-1-2
Conductors Solid, annealed aluminum, class 1 in accordance with GOST 22483-77
Insuliation PVC insulation compound type TI 1 in accordance with LST EN 50363-3
Cable colours Cores color in accordance with LST HD 308, green/yellow in accordance with LST EN 50396

See also

SL 1X1,5

Special-purpose wire is designed to identify fiber-optic or communication cable route. The wire is designed…


The wire is designed for industrial blasting operations. PE-insulated solid conductor is made out of…