Technical date
Conductor resistance at +20°C In accordance with LST EN 60228+AC
Conductor working temeprature, max. +70°C (under normal conditions) +160°C (in the event of short circuit)
Thermal shock 1 h at +150°C
Rated voltage U/U0 300/500 V
High voltage test, kV 2 kV
Operating temperatures Mounting -5°C - +40°C Operating -30°C -+70°C
Flame propagation Flame test in accordance with LST EN 60332-1-2
Construction
Conductors Stranded, annealed copper, class 2 in accordance with LST EN 60228+AC
Insuliation PVC insulation compound type TI 1 in accordance with LST EN 50363-3
Cable colours Cores color in accordance with LST HD 308, green/yellow in accordance with LST EN 50396